Basic
- Type: LAN cables
- Operating voltage: 150 V
- Voltage test: AC 50 Hz: 700 V # DC: 1000 V
- Insulation resistance: 5 GΩ x km
- Capacity: at 1 kHz: 50 ± 5 nF/km
Halogen-free, data transmission cable
Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2)
Halogen-free (EN 60754)
Low smoke emission (EN 61034)
Data transmissionDC loop resistance at 20 °C (max): 165 Ω/km
Resistance unbalance within a pair: ≤ 2 %
Capacitance unbalance pair to ground at 1 kHz (max): 1600 pF/km
Characteristic impedance at 100 MHz: 100 ± 5 Ω
BiTLAN U/UTP cat.6 350MHz LSOH cables are applicable to computer networks with operating frequency band up to 350MHz. Suitable for transmission of data, audio and video signals with bitrate up to 1Gb/s. Dedicated for fixed installations within indoor structured cabling systems as per EN 50173-1, ISO/IEC 11801, ANSI/TIA 568-C.2 standards, as well as within industrial networks not exposed to external electromagnetic interferences. Cables with flame retardant LSOH outer sheath ensuring low smoke emission acc. to EN 50268, IEC 61034-1(2) and limited emission of corrosive gases acc. to EN 50267, IEC 60754-2, should be installed in places with increased fire safety requirements. Cables classified according to EN 50575 (CPR).
| Cat. no. | Construction | Cu wire | Outer diameter [mm] | Approximate cable weight [kg/km] | Bandwidth [MHz] | |
| TI0049 | U/UTP cat.6 LSOH | 23AWG(0,54) | 5,8 | 38 | 350 |
Guidelines for laying electric cables in the ground