BiTflame®A(St)

Fire resistant, halogen-free control, power supply and telecommunication cable

Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
B2ca B2ca

Basic

  • Type: Fire resistant cables
  • Operating voltage: 150 V
  • Voltage test: AC: 1500 V # DC: 2250 V
  • Insulation resistance: 200 MΩxkm
  • Capacity: 150 nF/km
  • Min. bend radius of permanent connection: 10xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • Minimum installation temperature: -5°C

Pair loop resistance at 20 °C (max.):
0,6 mm: 135,8 Ω/km
0,8 mm: 75 Ω/km
1,0 mm: 48 Ω/km

Cable construction

  • Conductor material: copper wires
  • Core construction: Single-wire conductor
  • Insulation type: LSOH
  • Screen: foil screen
  • Core arrangement: paired/triple/quadruple cable
  • Sheath type: LSOH
  • Sheath color: red

Fire and functional properties

  • Low smoke emission EN 61034, Halogen-free
  • Fire classification: B2ca

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application

Certificates

  • CNBOP

Halogen-free special cables for interconnecting station equipment, telephone and teletransmission equipment and data transmission devices by means of analogue and digital signals in control and signalling fire protections systems. The cables are used primarily as transmission and power suplly lines for line equipment (sensors, linear modules) in supervised lines of fire signalling systems and autonomous fire extinguisher and smoke removal control systems. The cables are incorporated in systems used at the „0″ moment of fire origination (the moment of fire detection by the central detector). The cables can be used for transmitting trigger signals or conditions to auxiliary devices, which are activated by the central fire signalling mechanism upon detection of a fire (e.g. disconnection of a residential ventilation system, downward movement of passenger lifts, switching off of the power supply of building). Static screen protects the cable against interferences of external magnetic fields. The cables are CPR classification acc. to EN 50575.

Cat. no.n x mmOuter
diameter
[mm]
Approximate
cable weight
[kg/km]
BF00682x2x0,65,330
BF00693x2x0,65,739
BF00701x2x0,84,526
BF00711x4x0,85,140
BF00722x2x0,86,244
BF00733x2x0,87,061
BF00744x2x0,87,977
BF00755x2x0,88,692
BF00821x2x1,05,338
BF00831x4x1,06,360
BF00842x2x1,07,765
BF00853x2x1,08,691
BF00864x2x1,09,9116
BF00875x2x1,011,0139
Fire-resistant Cables and their key role in fire safety

Fire-resistant Cables and their key role in fire safety

Fire-resistant cables are a specialized type of cable…

Read
Fiber Optic Cables – efficient methods of data transmission

Fiber Optic Cables – efficient methods of data transmission

Fiber optic cables, which gained popularity at the…

Read
Fiber Optic Cables – Types and Symbol Meanings. Key aspects 

Fiber Optic Cables – Types and Symbol Meanings. Key aspects 

Fiber optic cables are essential for transmitting data…

Read