BiT LiYY 300/300 V

Flexible control cables with coloured conductors, rated 300/300V

Industrial application Industrial application
Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility High flexibility

Basic

  • Type: Control and power cables
  • Operating voltage: 300/300 V
  • Voltage test: 1500 V
  • Insulation resistance: 20 MΩ x km
  • Capacity: (at 800 Hz): 150 pF/m
  • Inductance: 0,65 mH/km
  • Min. bending radius of movable connections: 7,5xØ
  • Min. bend radius of permanent connection: 4xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -5°C
  • flexible connections up to: 80°C

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: PVC
  • Core arrangement: multi-core cable
  • Sheath type: PVC
  • Sheath color: grey

Flame retardant

  • For a single insulated cable

Installation conditions

  • Internal application
  • Flexible connections

Cables designed for signalling control circuits, control circuits in industrial applications, in measurement technology and for analogue and digital signals transmission in electronic industrial and automatic control engineering systems. For fixed installations and mobile/portable devices. Suitable for usage in internal systems, in both dry and damp rooms. Core arrangement ensures asymmetry attenuation of 10 dB. In the environment with considerable electromagnetic interference we recommend using a screened version – BiT LiYCY. Cables classified according to EN 50575 (CPR).

Cat. no.n x mm2Outer
diameter*
[mm]
Approximate
cable weight
[kg/km]
S300792×0,54,733
S300803×0,5540
S300814×0,55,548
S300825×0,5658
S300836×0,56,568
S300847×0,56,572
S300858×0,57,482
S3008610×0,58,497
S3008712×0,58,7112
S3008814×0,59,1128
S3008916×0,59,6144
S3009018×0,510,1162
S3009120×0,510,9184
S3009221×0,510,9188
S3009427×0,512,7252
S3009530×0,513,2268
S3009737×0,514,2322
S3009840×0,515,3360
S3009944×0,516,3404
S3010148×0,516,6430
S3010252×0,517460
S3010356×0,517,5492
S3010461×0,518,1530
S301052×0,755,141
S301063×0,755,450
S301074×0,75660
S301085×0,756,574
S301096×0,757,188
S301107×0,757,192
S301118×0,758105
S3011210×0,759,2124
S3011312×0,759,5144
S3011414×0,7510165
S3011516×0,7510,8192
S3011618×0,7511,3216
S3011720×0,7511,9240
S3011821×0,7511,9245
S3012027×0,7514,2330
S3012130×0,7514,4348
S3012337×0,7515,8427
S3012440×0,7517,2465
S301272×1,05,853
S301283×1,06,265
S301294×1,06,879
S301305×1,07,6100
S301316×1,08,3120
S301327×1,08,3125
S301338×1,09,2137
S3013410×1,010,8169
S3013512×1,011,1196
S3013614×1,011,7223
S3013716×1,012,4255
S3013818×1,013,5300
S3013920×1,014,1332
S301492×1,56,265
S301503×1,56,681
S301514×1,57,5103
S301525×1,58,2125
S301536×1,58,9150
S301547×1,58,9160
S301558×1,59,9174
S3015610×1,511,6215
S3015712×1,512250
S3015814×1,512,6285
S3015916×1,513,7338
S3016018×1,514,5380
S3016120×1,515,4430
S301712×2,57,8104
S301723×2,58,4130
S301734×2,59,3160
S301745×2,510,2196
S301756×2,511,3240
S301767×2,511,3255
S301778×2,513290
S3017810×2,514,9350
S3017912×2,515,6415
paired cables
Cat. no.n x 2 x mm2Outer
diameter*
[mm]
Approximate
cable weight
[kg/km]
S303422x2x0,56,955
S303433x2x0,5867
S303444x2x0,58,783
S303455x2x0,59,4105
S303466x2x0,59,7114
S303477x2x0,511,2138
S303488x2x0,511,7153
S3034910x2x0,512,6185
S3035012x2x0,513,8228
S3035114x2x0,514,7260
S3035216x2x0,516305
S3035318x2x0,516,7330
S3035420x2x0,517,2360
S3035524x2x0,517,7420
S303602x2x0,757,773
S303613x2x0,758,785
S303624x2x0,759,5106
S303635x2x0,7510,3134
S303657x2x0,7512,2176
S3036710x2x0,7514,2252
S3036812x2x0,7515,4301
S3036914x2x0,7516,3343
S3037016x2x0,7517,5395
S3037118x2x0,7518,5437
S303772x2x1,08,994
S303783x2x1,010110
S303794x2x1,011,1143
S303805x2x1,012,1181
S303827x2x1,014,5245
S3038410x2x1,016,6338
S3038512x2x1,017,7395
S3038614x2x1,019,1460
S3038716x2x1,020,4530
S3038818x2x1,021,6585
S303942x2x1,59,5116
S303953x2x1,511142
S303964x2x1,512180
S303975x2x1,513,4240
S303997x2x1,515,8315
S3040110x2x1,517,8427
S3040212x2x1,519,3510
S3040314x2x1,520,7595
S3040416x2x1,522,2680
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
BiTinstal® H (p) 450/750V – Safe and Reliable              Installation Cable

BiTinstal® H (p) 450/750V – Safe and Reliable Installation Cable

Safety is a top priority for all of…

Read