BiT Li2YCYv-TP

Data transmission cables, paired, with reduced capacitance and reinforced outer sheath, rated 300/300 V

Industrial application Industrial application
Indoor application Indoor application
Underground installation Underground installation
Outdoor application Outdoor application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility High flexibility
Electromagnetic compatibility Electromagnetic compatibility
Data transmission Data transmission

Basic

  • Type: Control and power cables
  • Operating voltage: 300/300 V
  • Voltage test: 1500 V
  • Insulation resistance: 5 GΩxkm
  • Capacity: max 75pF/km
  • Inductance: 0,70 mH/km
  • Min. bending radius of movable connections: 10xØ
  • Min. bend radius of permanent connection: 5xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -5°C
  • flexible connections up to: 80°C

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: PE
  • Screen: braided screen
  • Core arrangement: paired/triple/quadruple cable
  • Sheath type: PVC
  • Sheath color: black

Fire and functional properties

  • oxygen index >29

Flame retardant

  • For a single insulated cable

Installation conditions

  • Internal application
  • External application
  • Underground installation
  • Flexible connections

Environmental resistance

  • UV resistance

Cable designed for data transmission systems, for the transmission of analogue and digital signals. A common braided screen protects against the influence of external interference fields. Suitable for use indoors, in dry and humid areas, for outdoor applications and for direct burial. Outer sheath is UV resistant. Cables classified according to EN 50575 (CPR).

Cat. no.nx2xmm2Outer diameter
[mm]
Approximate
cable weight
[kg/km]
S318101x2x0,57,368
S318052x2x0,59,5110
S317853x2x0,510,6132
S317944x2x0,511,3155
S317866x2x0,512,4190
S318348x2x0,514,2235
S317831x2x0,758,390
S317842x2x0,7511,3150
S317871x2x1,08,8100
S317822x2x1,012,1175
S317933x2x1,013,3205
S317894x2x1,014,4240
S317906x2x1,015,9310
S317918x2x1,018,4390
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
BiTinstal® H (p) 450/750V – Safe and Reliable              Installation Cable

BiTinstal® H (p) 450/750V – Safe and Reliable Installation Cable

Safety is a top priority for all of…

Read