NHXH FE180/PH120/E90 MICA

Fire resistant, halogen free power cable

Industrial application Industrial application
Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
180 min. insulation resistance to fire (IEC 60331) 180 min. insulation resistance to fire (IEC 60331)
90 min. circuit integrity (VDE 4102-12) 90 min. circuit integrity (VDE 4102-12)
Sprinkler zones Sprinkler zones

Basic

  • Type: Fire resistant cables
  • Operating voltage: 0,6/1 kV

Operating temperature

  • fixed installation from: -30°C
  • fixed installation up to: 90°C
  • Minimum installation temperature: -5°C

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 1 or 2 (according to EN 60228, IEC 60228)
  • Insulation type: LSOH
  • Core arrangement: multi-core cable
  • Sheath type: LSOH
  • Sheath color: orange

Fire and functional properties

  • Fire resistant (IEC 60331), For use in sprinklers zone, Low smoke emission EN 61034, Fire integrity function (EN 50200, DIN 4102-12), Halogen-free

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application

Certificates

  • CNBOP, VDE

Fire resistant power and control cables have E90 fire integrity function which means the assurance of power supply or control under fire conditions for 90 minutes. They are intended for use in buildings with increased fire safety requirements due to high concentration of people, material and cultural assets of high value (sky scrapers, hospitals, shopping centres, tunnels, museums, cinemas, theatres). Cables can be used for power supply or control (lighting, lifts, fire-fighting equipment, pumps). They can be used in fixed installations inside buildings. In case of outdoor application cables should be secured against UV radiation and the external factors. Cables with improved fire characteristic E90 must be installed on the supporting systems tested according to DIN 4102-12.

Cat. no.n x mm2Outer
diameter
[mm]
Approximate
cable weight
[kg/km]
B642351×10 RE8,9188
B642361×16 RM10,5278
B642371×25 RM12,1391
B642381×35 RM13,2497
B642391×50 RM15,5674
B642401×70 RM16,9882
B642411×95 RM191178
B642421×120 RM20,71410
B642431×150 RM23,31789
B642441×185 RM252164
B642451×240 RM28,42739
B642461×300 RM30,93311
B642471×400 RM34,44169
B642481×500 RM39,35347,2
B642493×1,5 RE13,6259
B642503×2,5 RE14,4308
B642513×4 RE15,4377
B642523×6 RE16,5461
B642533×10 RE18,2623
B642543×16 RM21,6921
B642553×25 RM25,11318
B642563×35 RM27,71693
B642573×50 RM32,82355
B642583×70 RM35,83032
B642593×95 RM40,24054
B642603×120 RM44,14905
B642613×150 RM49,76258
B642623×185 RM53,97565
B642633×240 RM61,19646
B642644×1,5 RE14,6304
B642654×2,5 RE15,5365
B642664×4 RE16,7452
B642674×6 RE17,9559
B642684×10 RE19,8765
B642694×16 RM23,61141
B642704×25 RM27,61651
B642714×35 RM30,62136
B642724×50 RM36,32974
B642734×70 RM39,63847
B642744×95 RM44,85192
B642754×120 RM496252
B642764×150 RM55,78053
B642774×185 RM59,89666
B642784×240 RM67,912332
B642795×1,5 RE15,8354
B642805×2,5 RE16,8430
B642815×4 RE18536
B642825×6 RE19,4667
B642835×10 RE21,6920
B642845×16 RM25,81382
B642855×25 RM30,42023
B642865×35 RM342644
B642875×50 RM40,13658
B642885×70 RM44,24769
B642895×95 RM49,76409
B642905×120 RM54,87790
B642915×150 RM61,89951
B642925×185 RM66,511955
B642937×1,5 RE16,9417
B642947×2,5 RE18,1513
B642957×4 RE19,5649
B642967×6 RE20,7818
B642977×10 RE23,11147,2
B642987×16 RM27,91731,7
B642997×25 RM33,62615,4
B6430010×1,5 RE20,8557
B6430110×2,5 RE22,3690
B6430210×4 RE24,2881
B6430312×1,5 RE21,4625
B6430412×2,5 RE23781
B6430512×4 RE24,91005
B6430614×1,5 RE22,4701
B6430714×2,5 RE23,5787,1
B6430814×4 RE24,1882
B6430916×1,5 RE25,3990,3
B6431016×2,5 RE26,11140
B6431119×1,5 RE24,7874
B6431219×2,5 RE26,61111
B6431324×1,5 RE28,71079
B6431424×2,5 RE31,41405
B6431526×2,5 RE31,51525,9
B6431630×1,5 RE30,41283
B6431730×2,5 RE37,51964,3
B6431848×1,5 RE33,21679
B6431948×2,5 RE40,82551,7
B643351×10 RE8,9188
B643361×16 RM10,4278
B643371×25 RM12,1391
B643381×35 RM13,1497
B643391×50 RM15,3674
B643401×70 RM16,7882
B643411×95 RM18,91178
B643421×120 RM20,51410
B643431×150 RM231789
B643441×185 RM24,72164
B643451×240 RM28,32739
B643461×300 RM30,23311
B643471×400 RM34,44169
B643481×500 RM39,35347,2
B643493×1,5 RE13,3259
B643503×2,5 RE14,4308
B643513×4 RE15,4377
B643523×6 RE16,4461
B643533×10 RE18,1623
B643543×16 RM21,4921
B643553×25 RM25,11318
B643563×35 RM27,41693
B643573×50 RM32,52355
B643583×70 RM35,43032
B643593×95 RM40,34054
B643603×120 RM43,94905
B643613×150 RM49,26258
B643623×185 RM53,37565
B643633×240 RM61,29646
B643644×1,5 RE14,6304
B643654×2,5 RE15,5365
B643664×4 RE16,6452
B643674×6 RE17,8559
B643684×10 RE19,7765
B643694×16 RM23,41141
B643704×25 RM27,61651
B643714×35 RM30,32136
B643724×50 RM35,92974
B643734×70 RM39,33847
B643744×95 RM44,95192
B643754×120 RM48,86252
B643764×150 RM55,18053
B643774×185 RM609666
B643784×240 RM6812332
B643795×1,5 RE15,7354
B643805×2,5 RE16,8430
B643815×4 RE18536
B643825×6 RE19,3667
B643835×10 RE21,7920
B643845×16 RM25,61382
B643855×25 RM30,42023
B643865×35 RM33,72644
B643875×50 RM39,73658
B643885×70 RM43,74769
B643895×95 RM49,86409
B643905×120 RM54,57790
B643915×150 RM61,29951
B643925×185 RM65,811955
B643937×1,5 RE16,9417
B643947×2,5 RE18,1513
B643957×4 RE19,4649
B643967×6 RE21,1818
B643977×10 RE23,51147,2
B643987×16 RM27,91731,7
B643997×25 RM33,62615,4
B6440010×1,5 RE21,1557
B6440110×2,5 RE22,6690
B6440210×4 RE24,5881
B6440312×1,5 RE21,7625
B6440412×2,5 RE23,3781
B6440512×4 RE25,21005
B6440614×1,5 RE22,7701
B6440714×2,5 RE24,4787,1
B6440814×4 RE26,4882
B6440916×1,5 RE24,1990,3
B6441016×2,5 RE25,91140
B6441119×1,5 RE25,3874
B6441219×2,5 RE27,21111
B6441324×1,5 RE29,71079
B6441424×2,5 RE32,11405
B6441526×2,5 RE32,31525,9
B6441630×1,5 RE31,41283
B6441730×2,5 RE341964,3
B6441848×1,5 RE38,81679
B6441948×2,5 RE41,92551,7
Fire-resistant Cables and their key role in fire safety

Fire-resistant Cables and their key role in fire safety

Fire-resistant cables are a specialized type of cable…

Read
Coaxial Cables. Impedance, Attenuation, Applications.

Coaxial Cables. Impedance, Attenuation, Applications.

A coaxial cable is a specialized type of…

Read
BiTinstal® H (p) 450/750V – Safe and Reliable              Installation Cable

BiTinstal® H (p) 450/750V – Safe and Reliable Installation Cable

Safety is a top priority for all of…

Read