Basic
- Type: Servo motor cables
- Operating voltage: 3,6/6 kV
- Voltage test: 11kV
- Min. bend radius of permanent connection: 12xØ
Medium voltage cable for connections between motor and frequency converter (VFD)
Industrial application
Indoor application
Underground installation
Outdoor application
UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2)
Oil resistance (EN 60811-404)BiTservo 3GSEGCY 3,6/6 kV cables are designed for connection between frequency converters (VFD) and medium voltage motors. They are suitable for installation inside buildings in dry and damp rooms but also outdoors (resistance to UV and atmospheric conditions) or buried directly in ground. Cables classified according to EN 50575 (CPR).
| Cat. no. | n x mm2 | Outer diameter [mm] | Current-carrying capacity *) [A] | Capacitance [nF/km] | Approximate cable weight [kg/km] | |
| IP1100 | 3×35/18 | 46,6 | 169 | 280 | 3320 | |
| IP1101 | 3×50/25 | 50,4 | 203 | 300 | 4060 | |
| IP1102 | 3×70/35 | 54,5 | 253 | 350 | 5000 | |
| IP1103 | 3×95/50 | 59,3 | 306 | 390 | 6375 | |
| IP1104 | 3×120/60 | 63,3 | 352 | 420 | 7310 | |
| IP1105 | 3×150/75 | 67,9 | 400 | 460 | 8840 | |
| IP1106 | 3×185/95 | 71,0 | 451 | 500 | 10215 | |
| IP1107 | 3×240/120 | 77,8 | 523 | 560 | 12545 |