BiTmining®NTSCGEWOEU-W …/3

Medium voltage, flexible power supply cable for use in water based on DIN VDE 0250-813

Industrial application Industrial application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility High flexibility
Mechanical resistance Mechanical resistance
Oil resistance (EN 60811-404) Oil resistance (EN 60811-404)
Explosion hazard area Explosion hazard area
Open-pit mining Open-pit mining

Basic

  • Type: Mining cables
  • Operating voltage: 6/10 kV, 8,7/15 kV, 12/20 kV, 14/25 kV, 18/30 kV

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -25°C
  • flexible connections up to: 80°C

Max. permissible conductor temp.: 90 °C
Max. short-circuit temp. at conductor: 250 °C
De-rating factors: acc. to DIN VDE 0298-4
Max. tensile load per conductor: 15 N/mm²
Torsional stresses: +/-25 °/m

Cable construction

  • Conductor material: tinned copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: rubber
  • Core arrangement: multi-core cable
  • Sheath type: rubber
  • Sheath color: red

Fire and functional properties

  • oxygen index >29

Flame retardant

  • For a single insulated cable

Installation conditions

  • Mining applications
  • Laying in water
  • Flexible connections

Environmental resistance

  • UV resistance
  • Oil resistant EN 60811-404
  • Increased mechanical resistance
  • Water resistance

Certificates

  • WUG

Power supply cable for use in open-pit mining facilities designed for operation in water and exposed to high mechanical stresses, e.g. or connection to dredgers, floating docks, submersible pumps, etc. Cables are suitable to work in sewage, salt and brackish water.

BiTmining® NTSCGEWOEU-W …/3 3.6/6 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00013×25+3×25/345-480,7950,360,34131329401125
BM00023×35+3×25/347-500,5650,340,381624,336701575
BM00103×50+3×35/350-530,3930,320,442026,140212250
BM00033×50+3×25/350-530,3930,320,442026,139482250
BM00113×50+3×50/350-530,3930,320,442026,141272250
BM00043×70+3×35/356-590,2770,310,482508,551573150
BM00053×95+3×50/360-630,210,290,5430111,662104275
BM00123×95+3×70/360-630,210,290,5430111,663834275
BM00063×120+3×70/362-650,1640,280,5935214,672405400
BM00133×150+3×25/369-720,1640,280,5935214,682995400
BM00073×150+3×70/369-720,1320,280,6440418,386516750
BiTmining® NTSCGEWOEU-W …/3 6/10 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00153×25+3×25/346-490,7950,370,31131330871125
BM00253×35+3×16/348-510,5650,350,351624,333781575
BM00163×35+3×25/348-510,5650,350,351624,334671575
BM00263×35+3×35/348-510,5650,350,351624,335401575
BM00173×50+3×25/353-560,3930,330,392026,143392250
BM00273×50+3×50/353-560,3930,330,392026,145182250
BM00183×70+3×35/357-600,2770,310,432508,553623150
BM00283×95+3×35/361-640,210,30,4930111,663034275
BM00193×95+3×50/361-640,210,30,4930111,664094275
BM00203×120+3×70/365-680,1640,290,5335214,677235400
BiTmining® NTSCGEWOEU-W …/3 8.7/15 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00303×25+3×25/353-560,7950,390,25139338251125
BM00293×25+3×16/353-560,7950,390,25139337361125
BM00313×35+3×25/355-580,5650,370,281724,342361575
BM00323×50+3×25/359-620,3930,350,312156,149342250
BM00333×70+3×35/362-650,2770,330,342658,559743150
BM00343×95+3×50/368-710,210,320,3931911,673674275
BiTmining®NTSCGEWOEU-W …/3 12/20 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00403×25+3×25/357-600,7950,410,22139343341125
BM00393×25+3×16/357-600,7950,410,22139342451125
BM00413×35+3×25/360-630,5650,390,241724,347651575
BM00423×50+3×25/365-680,3930,370,272156,157682250
BM00483×50+3×35/365-680,3930,370,272156,158412250
BM00433×70+3×35/369-720,2770,350,32658,568573150
BiTmining®NTSCGEWOEU-W …/3 14/25 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00503×25+3×25/365-680,7950,430,1913913953291125
BM00513×35+3×25/367-700,5650,410,2117217257941575
BiTmining®NTSCGEWOEU-W …/3 18/30 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Current
carrying
capacity
at 30°C
[A]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM00603×25+3×25/370-730,7950,450,17139360751125
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
What Internet Cables to Use? Types of Network Cables. 

What Internet Cables to Use? Types of Network Cables. 

Basic network cables forming the foundation....

Read