BiTmining® (N)TSCGEWOEU-F

Medium voltage, flexible power supply cable for fixed installations

Industrial application Industrial application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility High flexibility
Mechanical resistance Mechanical resistance
Oil resistance (EN 60811-404) Oil resistance (EN 60811-404)
Low operating temperature Low operating temperature
Open-pit mining Open-pit mining

Basic

  • Type: Mining cables
  • Operating voltage: 3,6/6 kV, 6/10 kV, 8,7/15 kV, 12/20 kV, 14/25 kV, 18/30 kV

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -25°C
  • flexible connections up to: 80°C

Max. permissible conductor temp.: 90 °C
Max. short-circuit temp. at conductor: 250 °C
De-rating factors: acc. to DIN VDE 0298-4

Max. tensile load per conductor: 15 N/mm²
Torsional stresses: +/-100 °/m
Bending radius: acc. to DIN VDE 0298-3

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: rubber
  • Core arrangement: multi-core cable
  • Sheath type: rubber
  • Sheath color: red

Fire and functional properties

  • oxygen index >29

Flame retardant

  • For a single insulated cable

Installation conditions

  • Mining applications
  • External application
  • Laying in water
  • Flexible connections

Environmental resistance

  • Oil resistant EN 60811-404
  • Increased mechanical resistance
  • UV resistance

Flexible power supply cable for fixed and semi-fixed installations used in the area of opencast technology. Typical operations are: alongside conveyor systems, connection cables for transformers, on spreaders or bucket wheel excavators with continuous slight movements like free overhang or twisting.

BiTmining®(N)TSCGEWOEU-F 3.6/6 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM01503×25+3×25/339-420,780,330,453,624881125
BM01513×25+3×50/347-500,780,360,453,633291125
BM01523×35+3×25/343-460,5540,310,5529381575
BM01533×35+3×50/347-500,5540,330,5534921575
BM01543×50+3×25/346-490,3860,30,587,235482250
BM01553×50+3×50/347-500,3860,30,587,238592250
BM01563×70+3×35/350-530,2720,290,641044973150
BM01573×70+3×50/350-530,2720,290,641046033150
BM01583×95+3×50/355-580,2060,270,7313,655404275
BM01593×120+3×70/358-610,1610,260,817,266985400
BM01603×150+3×70/362-650,1290,260,8821,577866750
BM01613×185+3×95/369-720,1060,250,9426,595578325
BiTmining®(N)TSCGEWOEU-F 6/10 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM01703×25+3×25/341-440,780,340,43,626581125
BM01713×25+3×50/346-490,780,360,43,632871125
BM01723×35+3×25/344-470,5540,320,45530181575
BM01733×35+3×50/347-500,5540,340,45534921575
BM01743×50+3×25/347-500,3860,30,517,236352250
BM01693×50+3×35/347-500,3860,30,517,236952250
BM01753×50+3×50/347-500,3860,30,517,238152250
BM01763×70+3×35/351-540,2720,290,571045903150
BM01773×70+3×50/351-540,2720,290,571046973150
BM01783×95+3×50/356-590,2060,280,6513,657904275
BM01793×120+3×70/359-620,1610,270,7117,268065400
BM01803×150+3×70/364-670,1290,260,7821,581396750
BiTmining®(N)TSCGEWOEU-F 8.7/15 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM01853×25+3×25/341-440,780,360,323,626581125
BM01863×25+3×50/346-490,780,380,323,632871125
BM01873×35+3×25/344-470,5540,340,36530181575
BM01883×35+3×50/347-500,5540,340,36534921575
BM01893×50+3×25/347-500,3860,320,417,236352250
BM01903×50+3×50/347-500,3860,320,417,238152250
BM01913×70+3×35/351-540,2720,310,451046433150
BM01923×70+3×50/351-540,2720,310,451047433150
BM01933×95+3×50/356-590,2060,290,5113,657904275
BM01943×120+3×70/359-620,1610,280,5617,268065400
BM01953×150+3×70/364-670,1290,280,621,581396750
BiTmining®(N)TSCGEWOEU-F 12/20 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM02003×25+3×25/349-520,780,380,283,633721125
BM02013×25+3×50/349-520,780,380,283,635521125
BM02023×35+3×25/351-540,5540,360,31537661575
BM02033×35+3×50/351-540,5540,360,31539461575
BM02043×50+3×25/356-590,3860,340,357,246192250
BM02053×50+3×50/356-590,3860,340,357,247992250
BM02063×70+3×35/359-620,2720,320,381056443150
BM02073×70+3×50/359-620,2720,320,381057503150
BM02083×95+3×50/365-680,2060,310,4313,669734275
BM02093×120+3×70/367-700,1610,30,4717,280385400
BiTmining®(N)TSCGEWOEU-F 14/25 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM02203×25+3×25/354-570,780,40,243,640231125
BM02213×25+3×50/354-570,780,40,243,642041125
BM02223×35+3×25/357-600,5540,370,26544451575
BM02233×35+3×50/357-600,5540,370,26546251575
BM02243×50+3×25/360-630,3860,350,37,251582250
BM02253×50+3×50/360-630,3860,350,37,253392250
BM02263×70+3×35/365-680,2720,340,331064573150
BM02273×70+3×50/365-680,2720,340,331065633150
BiTmining®(N)TSCGEWOEU-F 18/30 kV
Cat. non x mm2Outer diameter
min. – max.
[mm]
Conductor
resistance
at 20°C
[Ω/km]
Inductance
[mH/km]
Operating
capacitance
[μF/km]
Permissible
short-circuit
current (1s)
[kA]
Approximate
cable
weight
[kg/km]
Maximum
permissible
tensile force
[N]
BM02403×25+3×25/358-610,780,410,213,644421125
BM02413×25+3×50/358-610,780,410,213,646221125
BM02423×35+3×25/360-630,5540,390,24548791575
BM02433×35+3×50/360-630,5540,390,24550591575
BM02443×50+3×25/365-680,3860,370,267,258582250
BM02453×50+3×50/365-680,3860,370,267,260382250
BM02463×70+3×35/369-720,2720,350,291069563150
BM02473×70+3×50/369-720,2720,350,291070633150
Fiber Optic Cables – efficient methods of data transmission

Fiber Optic Cables – efficient methods of data transmission

Fiber optic cables, which gained popularity at the…

Read
Fiber Optic Cables – Types and Symbol Meanings. Key aspects 

Fiber Optic Cables – Types and Symbol Meanings. Key aspects 

Fiber optic cables are essential for transmitting data…

Read
How to Select a Servo Cable for a Motor? The most important aspects

How to Select a Servo Cable for a Motor? The most important aspects

Frequency converters play a crucial role in various...

Read