BiTflame®AS(St) FE180/PH120/E90

Fire resistant, halogen-free cable

Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
180 min. insulation resistance to fire (IEC 60331) 180 min. insulation resistance to fire (IEC 60331)
90 min. circuit integrity (EN 50200) 90 min. circuit integrity (EN 50200)
B2ca B2ca
120 min. circuit integrity (EN 50200) 120 min. circuit integrity (EN 50200)

Basic

  • Type: Fire resistant cables
  • Operating voltage: 225 V
  • Voltage test: Test voltage: AC 1500 V; DC 2250 V
  • Insulation resistance: 500MΩxkm
  • Min. bend radius of permanent connection: 10xØ

Operating temperature

  • fixed installation from: -25°C
  • fixed installation up to: 70°C
  • Minimum installation temperature: -5°C

Pair loop resistance at 20 °C (maximum):
0,8mm – 75 Ω/km
1,0mm – 48 Ω/km
1,4mm – 26,6 Ω/km
1,8mm – 14,96 Ω/km
2,3mm – 9,6 Ω/km
2,8mm – 6,4 Ω/km

Cable construction

  • Conductor material: copper wires
  • Core construction: Single-wire conductor
  • Screen: foil screen
  • Sheath color: red

Fire and functional properties

  • Halogen-free, Low smoke emission EN 61034, Fire integrity function (EN 50200, DIN 4102-12)
  • Fire classification: B2ca

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application
  • Safety systems: DSO

Fire resistant, halogen-free cables designed for emergency lighting installations, alarm- , signalling-, and teletransmission systems, in sound alarm systems as well as in fire warning systems, fire automation and other safety ensuring installations. Static screen (St) protects the cable against interferences of external magnetic fields. Under fire conditions those cables ensure proper operation of installations for at least 120 minutes (PH120) and durability of conductors insulation for 180 minutes (FE180). During burning cables do not emit corrosive gases or dense smoke. Cables are suitable for fixed installations inside buildings. BiTflame®AS(St) FE180/PH120/E90 cables have been tested in accordance with the requirements of DIN 4102 p.12 and can be installed in E90 cable support systems as their elements (installation on clamps located every 30 cm and 60 cm).

Cat. no.n x 2 x mmApproximate outer diameter [mm]Calculated cable weight [kg/km]
B110201x2x0,85,736
B110212x2x0,87,969
B110223x2x0,88,779
B110234x2x0,810100
B110245x2x0,810,9127
B110258x2x0,812,7174
B110261x2x1,06,245
B110272x2x1,08,889
B110294x2x1,011,2132
B110305x2x1,012,3170
B110318x2x1,014,2235
B110321x2x1,47,466
B110332x2x1,410,6140
B110344x2x1,413,7211
B110351x2x1,88,9102
B110361x2x2,310,1141
B110372x2x2,314,7302
B110381x2x2,811,3189
Downloads
Fire-resistant Cables and their key role in fire safety

Fire-resistant Cables and their key role in fire safety

Fire-resistant cables are a specialized type of cable…

Read
Fiber Optic Cables – efficient methods of data transmission

Fiber Optic Cables – efficient methods of data transmission

Fiber optic cables, which gained popularity at the…

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read