Basic
- Type: Fire resistant cables
- Operating voltage: 150/250 V
- Voltage test: #AC 1500V # DC 2250V
- Insulation resistance: (minimum) 500MΩ*km
- Inductance: 0,7mH/km
- Min. bend radius of permanent connection: 10xØ
Fire resistant, halogen-free telecommunication cable
Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754)
Low smoke emission (EN 61034)
180 min. insulation resistance to fire (IEC 60331)
90 min. circuit integrity (EN 50200)
90 min. circuit integrity (VDE 4102-12)Pair loop resistance at 20 °C (maximum):
0,8 mm – 75 Ω/km
1,0 mm – 48 Ω/km
1,4 mm – 26,6 Ω/km
1,8 mm – 14,96 Ω/km
2,3 mm – 9,6 Ω/km
2,8 mm – 6,4 Ω/km
Fire resistant, halogen-free telecommunication cables designed for emergency lighting installations, alarm- , signalling-, and teletransmission systems, in sound alarm systems as well as in fire warning systems, fire automation and other safety ensuring installations. Static screen (St) protects the cable against interferences of external magnetic fields. Under fire conditions those cables ensure proper operation of installations for at least 90 minutes (PH90) and durability of conductors insulation for 3h (FE180). During burning cables do not emit corrosive gases or dense smoke. Cables are suitable for fixed installations inside buildings. BiTflame AS(St) FE180/E90cables have been tested in accordance with the requirements of DIN 4102 p.12 and can be installed in E90 cable support systems as their elements (installation on clamps located every 30cm and 60cm).
| Cat. no. | n x mm2 | Outer diameter [mm] | Approximate cable weight [kg/km] |
| BF0300 | 1x2x0,8 | 6,5 | 54 |
| BF0301 | 1x4x0,8 | 7,3 | 75 |
| BF0302 | 2x2x0,8 | 8,7 | 85 |
| BF0303 | 3x2x0,8 | 9,4 | 105 |
| BF0304 | 4x2x0,8 | 10,7 | 129 |
| BF0305 | 5x2x0,8 | 11,6 | 151 |
| BF0306 | 7x2x0,8 | 12,7 | 188 |
| BF0307 | 8x2x0,8 | 13,3 | 207 |
| BF0308 | 10x2x0,8 | 14,7 | 247 |
| BF0309 | 20x2x0,8 | 18,6 | 438 |
| BF0310 | 1x2x1,0 | 7,1 | 66 |
| BF0311 | 1x4x1,0 | 8 | 94 |
| BF0312 | 2x2x1,0 | 9,6 | 105 |
| BF0313 | 3x2x1,0 | 10,4 | 134 |
| BF0314 | 4x2x1,0 | 11,9 | 166 |
| BF0315 | 5x2x1,0 | 13 | 195 |
| BF0316 | 7x2x1,0 | 14,3 | 248 |
| BF0317 | 8x2x1,0 | 14,9 | 274 |
| BF0318 | 10x2x1,0 | 16,6 | 330 |
| BF0319 | 1x2x1,4 | 8,2 | 90 |
| BF0320 | 1x4x1,4 | 9,3 | 137 |
| BF0321 | 2x2x1,4 | 11,4 | 152 |
| BF0322 | 3x2x1,4 | 12,4 | 199 |
| BF0323 | 4x2x1,4 | 14,3 | 251 |
| BF0324 | 5x2x1,4 | 15,6 | 299 |
| BF0325 | 7x2x1,4 | 17,2 | 405 |
| BF0326 | 8x2x1,4 | 18,4 | 450 |
| BF0327 | 10x2x1,4 | 20,5 | 545 |
| BF0328 | 1x2x1,8 | 9,7 | 118 |
| BF0329 | 1x4x1,8 | 11,1 | 186 |
| BF0330 | 2x2x1,8 | 13,6 | 205 |
| BF0331 | 3x2x1,8 | 14,9 | 273 |
| BF0332 | 4x2x1,8 | 17,1 | 348 |
| BF0333 | 5x2x1,8 | 19,1 | 436 |
| BF0334 | 7x2x1,8 | 21 | 570 |
| BF0335 | 8x2x1,8 | 22 | 637 |
| BF0336 | 10x2x1,8 | 25 | 799 |
| BF0337 | 1x2x2,3 | 11 | 159 |
| BF0338 | 1x4x2,3 | 12,5 | 262 |
| BF0339 | 2x2x2,3 | 15,5 | 283 |
| BF0340 | 3x2x2,3 | 17 | 386 |
| BF0341 | 4x2x2,3 | 20,1 | 515 |
| BF0342 | 5x2x2,3 | 22 | 622 |
| BF0343 | 7x2x2,3 | 24,7 | 847 |
| BF0344 | 8x2x2,3 | 25,8 | 949 |
| BF0345 | 10x2x2,3 | 29,2 | 1187 |
| BF0346 | 1x2x2,8 | 12,2 | 209 |
| BF0347 | 1x4x2,8 | 14 | 354 |
| BF0348 | 2x2x2,8 | 17,4 | 378 |
| BF0349 | 3x2x2,8 | 19,6 | 541 |
| BF0350 | 4x2x2,8 | 22,7 | 698 |