BiTflame®AS FE 180/E90

Fire resistant, halogen-free telecommunication cable

Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
180 min. insulation resistance to fire (IEC 60331) 180 min. insulation resistance to fire (IEC 60331)
90 min. circuit integrity (EN 50200) 90 min. circuit integrity (EN 50200)
90 min. circuit integrity (VDE 4102-12) 90 min. circuit integrity (VDE 4102-12)

Basic

  • Type: Fire resistant cables
  • Operating voltage: 150/250 V
  • Voltage test: #AC 1500V # DC 2250V
  • Insulation resistance: (minimum) 500MΩ*km
  • Inductance: 0,7 mH/km
  • Min. bend radius of permanent connection: 10xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • Minimum installation temperature: -5°C

Pair loop resistance at 20 °C (maximum):
0,8 mm – 75 Ω/km
1,0 mm – 48 Ω/km
1,4 mm – 26,6 Ω/km
1,8 mm – 14,96 Ω/km
2,3 mm – 9,6 Ω/km
2,8 mm – 6,4 Ω/km

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 1 (according to EN 60228, IEC 60228)
  • Core arrangement: multi-core cable
  • Sheath color: red

Fire and functional properties

  • Halogen-free, Fire resistant (IEC 60331), Low smoke emission EN 61034

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application

Fire resistant, halogen-free telecommunication cables designed for emergency lighting installations, alarm- , signalling-, and teletransmission systems, in sound alarm systems as well as in fire warning systems, fire automation and other safety ensuring installations. Under fire conditions those cables ensure proper operation of installations for at least 90 minutes (PH90) and durability of conductors insulation for 180 minutes (FE180). During burning cables do not emit corrosive gases or dense smoke. Cables are suitable for fixed installations inside buildings. BiTflame®AS FE180/E90 cables have been tested in accordance with the requirements of DIN 4102 p.12 and can be installed in E90 cable support systems as their elements (installation on clamps located every 30 cm and 60 cm).

Cat. no.n x mm2Outer diameter
[mm]
Approximate
cable weight
[kg/km]
BF02401x2x0,85,237
BF02411x4x0,8655
BF02422x2x0,87,562
BF02433x2x0,88,281
BF02444x2x0,89,5101
BF02455x2x0,810,4121
BF02467x2x0,811,5167
BF02478x2x0,812,4185
BF024810x2x0,813,9223
BF024920x2x0,817,7408
BF02501x2x1,05,847
BF02511x4x1,06,773
BF02522x2x1,08,481
BF02533x2x1,09,2106
BF02544x2x1,010,7135
BF02555x2x1,012,1174
BF02567x2x1,013,4225
BF02578x2x1,014250
BF025810x2x1,015,7303
BF02591x2x1,46,969
BF02601x4x1,48113
BF02612x2x1,410,1123
BF02623x2x1,411,2167
BF02634x2x1,413,4227
BF02645x2x1,414,8274
BF02657x2x1,416,3360
BF02668x2x1,417,5420
BF026710x2x1,49,6512
BF02681x2x1,88,494
BF02691x4x1,89,7160
BF02702x2x1,812,7183
BF02713x2x1,814250
BF02724x2x1,816,2321
BF02735x2x1,818,2407
BF02747x2x1,820,1538
BF02758x2x1,821,1603
BF027610x2x1,823,9750
BF02771x2x2,39,6132
BF02781x4x2,311,2232
BF02792x2x2,314,6259
BF02803x2x2,316,1359
BF02814x2x2,319,2484
BF02825x2x2,321,1588
BF02837x2x2,323,6798
BF02848x2x2,324,7898
BF028510x2x2,327,71103
BF02861x2x2,810,8179
BF02871x4x2,813332
BF02882x2x2,816,5351
BF02893x2x2,818,7511
BF02904x2x2,821,8664
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
Fire-resistant Cables and their key role in fire safety

Fire-resistant Cables and their key role in fire safety

Fire-resistant cables are a specialized type of cable…

Read
Coaxial Cables. Impedance, Attenuation, Applications.

Coaxial Cables. Impedance, Attenuation, Applications.

A coaxial cable is a specialized type of…

Read