BiT LiYCY 300/300 V

Flexible control cables with coloured conductors, rated 300/300V

Industrial application Industrial application
Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility High flexibility
Electromagnetic compatibility Electromagnetic compatibility

Basic

  • Type: Control and power cables
  • Operating voltage: 300/300 V, 300/300 V
  • Voltage test: (50 Hz): 1500 V
  • Insulation resistance: 20 MΩ x km
  • Capacity: (at 800 Hz): Core/core - 150 pF/m, Core/screen - 2700 pF/m
  • Inductance: 0,65 mH/km
  • Min. bending radius of movable connections: 10xØ
  • Min. bend radius of permanent connection: 5xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -5°C
  • flexible connections up to: 80°C

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: PVC
  • Screen: braided screen
  • Core arrangement: multi-core cable
  • Sheath type: PVC
  • Sheath color: grey

Flame retardant

  • For a single insulated cable

Installation conditions

  • Internal application

The cables are intended for signalling control circuits, control circuits in industrial applications, in measurement technology, and for analogue and digital signals transmission in electronic industrial and automatic control engineering systems. For fixed installation, and mobile/portable devices. Suitable for use indoors, in both dry and damp rooms. A common screen of tinned copper wire braid ensures very good protection against external electromagnetic fields (approximately 50 dB). Cables classified according to EN 50575 (CPR).

Cat. no.n x mm2Outer
diameter*
[mm]
Approximate
cable weight
[kg/km]
S305872×0,55,342
S305883×0,55,650
S305894×0,56,258
S305905×0,56,774
S305916×0,57,285
S305927×0,57,288
S305938×0,58100
S3059410×0,59,1120
S3059512×0,59,3134
S3059614×0,59,8150
S3059716×0,510,5175
S3059818×0,511193
S3059920×0,511,7211
S3060021×0,511,7214
S3060227×0,513,4271
S3060330×0,513,8294
S3060537×0,515,1356
S3060640×0,516,3390
S3060744×0,517,3442
S3060948×0,517,5470
S3061052×0,518503
S3061156×0,518,6537
S3061361×0,519,1577
S306152×0,755,850
S306163×0,756,159
S306174×0,756,775
S306185×0,757,288
S306196×0,757,9104
S306207×0,757,9109
S306218×0,758,7125
S3062210×0,759,9148
S3062312×0,7510,2173
S3062414×0,7510,8193
S3062516×0,7511,5217
S3062618×0,7512,4251
S3062720×0,7513,1275
S3062821×0,7513,1280
S3063127×0,7514,8348
S3063230×0,7515,3383
S3063537×0,7517,8465
S3063640×0,7519522
S306372×1,06,558
S306383×1,06,976
S306394×1,07,692
S306405×1,08,3110
S306416×1,09131
S306427×1,09137
S306438×1,09,9159
S3064410×1,011,4194
S3064512×1,011,7220
S3064614×1,012,7256
S3064716×1,013,5291
S3064818×1,014,3330
S3064920×1,015,2365
S3065021×1,015,2370
S3065327×1,017,4479
S3065430×1,017,9521
S3065637×1,019,4625
S306572×1,57,174
S306583×1,57,594
S306594×1,58,4116
S306605×1,59,1141
S306616×1,59,9169
S306627×1,59,9177
S306638×1,511210
S3066410×1,513259
S3066512×1,513,4295
S3066614×1,514,2340
S3066716×1,515,1386
S3066818×1,515,8431
S3066920×1,517,2502
S3067021×1,517,2510
S3067327×1,519,3632
S3067430×1,520690
S3067637×1,521,7834
S306772×2,58,5126
S306783×2,59168
S306794×2,510195
S306805×2,510,9210
S306816×2,511,9278
S306827×2,511,9296
S306838×2,513,6345
S3068410×2,515,8403
S3068512×2,516,5540
S3068614×2,517,5589
S3068716×2,518,7640
S3068818×2,519,6681
S3068920×2,521,1762
S3069021×2,521,1816
paired cables
Cat. no.n x 2 x mm2Outer
diameter*
[mm]
Approximate
cable weight
[kg/km]
S308492x2x0,57,782
S308503x2x0,58,692
S308514x2x0,59,3111
S308525x2x0,510137
S308536x2x0,510,3149
S308547x2x0,511,8174
S308558x2x0,512,3191
S3085610x2x0,513,6237
S3085712x2x0,514,4272
S3085814x2x0,515,5314
S3085916x2x0,516,8370
S3086018x2x0,517,5399
S3086120x2x0,518431
S3086224x2x0,518,7499
S308642x2x0,758,397
S308653x2x0,759,3112
S308664x2x0,7510,1141
S308675x2x0,7511,1177
S308697x2x0,7513,2228
S3087110x2x0,7514,8297
S3087212x2x0,7516349
S3087314x2x0,7517,1410
S3087416x2x0,7518,5476
S3087518x2x0,7519,3512
S308772x2x1,09,5121
S308783x2x1,010,8150
S308794x2x1,011,7179
S308805x2x1,013,1232
S308827x2x1,015,3298
S3088410x2x1,017,4405
S3088512x2x1,018,7476
S3088614x2x1,019,9538
S3088716x2x1,021,4622
S3088818x2x1,022,4673
S308902x2x1,510,1145
S308913x2x1,511,6178
S308924x2x1,512,6218
S308935x2x1,514285
S308957x2x1,516,4366
S3089710x2x1,518,8508
S3089812x2x1,520,1588
S3089914x2x1,521,5678
S3090016x2x1,523774
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
BiTinstal® H (p) 450/750V – Safe and Reliable              Installation Cable

BiTinstal® H (p) 450/750V – Safe and Reliable Installation Cable

Safety is a top priority for all of…

Read