Basic
- Type: Data transmission and telecommunication cables
- Operating voltage: Not specified
- Voltage test: 1.5 kV
- Insulation resistance: 1 GΩxkm
- Capacity: 35 nF/km
- Min. bend radius of permanent connection: 10xØ
LiO2YS(St)CY, Data transmission cables for Profibus network
Industrial application
Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2)
High flexibility
Electromagnetic compatibility
Data transmissionWave impedance: 150 Ω +/- 10%
Conductor loop resistance (max.): 172 Ω/km
Screen resistance (max.): 9,7 Ω/km
Wave attenuation at a frequency of:
4 MHz = 2,5 dB/100m
16 MHz = 5,2 dB/100m
The cables are intended for connecting L2-BUS components (standard 485) and transmission of analogue and digital signals. Paired construction ensures good symmetry with respect to earth, while the double screen protects against interferences from external electromagnetic fields, what guarantees very good transmission quality. Cables may be used in dry and damp rooms, and are suitable for fixed installations and mobile devices. Cables classified according to EN 50575 (CPR).
| Cat. no. | n x 2 x mm | Outer diameter [mm] | Approximate cable weight [kg/km] |
| EB0008 | 1x2x0,64 (7×0,21) | 7,6 | 57 |