Details

Search results
Visualization Description

HTKSH FE180/PH120/E90

Fire resistant, halogen-free telecommunication cable
Indoor application Vertical flame propagation for a single cable (EN 60332-1) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Halogen-free (EN 60754) Low smoke emission  (EN 61034) 120 min. circuit integrity (EN 50200) Sprinkler zones 180 min. insulation resistance to fire (IEC 60331) 90 min. circuit integrity (VDE 4102-12)

Download:

Technical data:

Basic:

  • Cable type: Telecommunication cable
  • Test voltage: Napięcie przemienne: 1500 V
    Napięcie stałe: 2250 V

Installation details:

  • Application in sprinkler protected rooms
  • Indoor cable
  • Min. installation temperature: -5℃

Environmental resistance:

  • Halogen-free
  • Flame retardance on a single wire
  • Flame retardance on a bunched wires

Cable construction:

Basic:

  • Conductor: bare copper conductors
  • Conductor stranding: solid round copper conductor

Application:

Fire resistant, halogen-free telecommunication cables designed for emergency lighting installations, alarm- , signalling-, and teletransmission systems, in sound alarm systems as well as in fire warning systems, fire automation and other safety ensuring installations. Under fire conditions those cables ensure proper operation of installations for at least 120 minutes (PH120) and durability of conductors insulation for 180 minutes (FE180). During burning cables do not emit corrosive gases or dense smoke. Cables are suitable for fixed installations inside buildings. HTKSH FE180/PH120 (E90) cables have been tested in accordance with the requirements of DIN 4102 p.12 and can be installed in E90 cable support systems as their elements (installation on clamps located every 30 cm and 60 cm).