Details



Search results
Visualization Description

BiTmining® NTMCGCWOEU

Medium voltage, screened single core cable according to DIN VDE 0250-813
Industrial application UV resistant Vertical flame propagation for a single cable (EN 60332-1) Oxygen index High flexibility Oil resistance (EN 60811-404) Mining applications

Download:

Technical data:

Basic:

  • Cable type: Power cable
  • Operating voltage: Not specified

Operating temperature:

  • Fixed installation: -40℃ do 80℃
  • Flexible connections: -25℃ do 80℃
Max. tensile load per conductor: 15 N/mm²
Bending radius:
- fixed installation: ≥ 6 x outer-Ø
- free moving: ≥ 10 x outer-Ø

Installation details:

  • Flexible connections

Environmental resistance:

  • Flame retardance on a single wire
  • UV resistance
  • LOI >29
  • Enhanced oil resistance

Certificates and approvals:

  • CPR Certificates / DoP

Cable construction:

Basic:

  • Conductor: tinned copper conductors
  • Conductor stranding: class 5 (acc. to EN 60228, IEC 60228)
  • Core arrangement: single core cable

Application:

Flexible high voltage cable used in short lengths, e.g. as a connection in switch-gear or transformer houses where small bending radius is requested.



Back