Details

Search results
Visualization Description

BiT RE-2Y(St)Y-FR PiMF, 500V

PVC sheathed instrumentation cables with collective electrostatic screen and individually screened pairs, rated 500V
Industrial application Indoor application UV resistant Vertical flame propagation for a single cable (EN 60332-1) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Data transmission Classified according to EN 50575

Download:

Technical data:

Basic:

  • Cable type: Data transmission cable
  • Operating voltage: 300/500V
  • Test voltage: żyła/żyła 2000V
    żyła/ekran 2000V
  • Insulation resistance: >5 GΩxkm
  • Min. bending radius (fixed installations): 7,5 x Ø

Operating temperature:

  • Fixed installation: -40℃ do 80℃
  • Flexible connections: -5℃ do 80℃

Installation details:

  • Indoor cable
  • Min. installation temperature: -5℃

Environmental resistance:

  • Flame retardance on a single wire
  • Flame retardance on a bunched wires
  • UV resistance

Certificates and approvals:

  • CPR Certificates / DoP

Cable construction:

Basic:

  • Conductor: bare copper conductors
  • Conductor stranding: class 2 (acc. to EN 60228, IEC 60228)
  • Screen: double screen
  • Core arrangement: pairs / triples / quads

Application:

Cables designed for data transmission in numerical control systems ensuring optimum transmission of data up to 200 Kbit/s. Screened pairs twisted together ensure very good crosstalk attenuation and collective electrostatic screen protects against external interferences. Cables are suitable for application indoor and in dry and damp rooms. Outer sheath is UV resistant. Cables classified according to EN 50575 (CPR).



Back