BiTflame®1000 FE180/PH120/E90

Fire resistant, halogen-free control and power supply cables, rated 0,6/1kV
Industrial application Indoor application Outdoor application UV resistant Vertical flame propagation for a single cable (EN 60332-1) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Halogen-free (EN 60754) Low smoke emission  (EN 61034) 180 min. insulation resistance to fire (IEC 60331) 90 min. circuit integrity (VDE 4102-12) Sprinkler zones 120 min. circuit integrity (EN 50200)

Download:

Technical data:

Basic:

  • Cable type: Power cable
  • Operating voltage: 0,6/1kV
  • Test voltage: 3500 V
  • Insulation resistance: > 200 MΩ x km
  • Min. bending radius (fixed installations): 10 x Ø

Operating temperature:

  • Fixed installation: -40℃ do 90℃
Permissible conductor operating temperature: 90°C
Permissible conductor temperature during short circuit: 250°C

Installation details:

  • Application in sprinkler protected rooms
  • Indoor cable
  • Outdoor cable
  • Min. installation temperature: -5℃

Environmental resistance:

  • Halogen-free
  • Flame retardance on a single wire
  • Flame retardance on a bunched wires
  • UV resistance
  • Fire resistance (acc. to IEC 60331)
  • Fire integrity function (EN 50200, DIN 4102-12)

Certificates and approvals:

  • CNBOP

Cable construction:

Basic:

  • Conductor: bare copper conductors
  • Conductor stranding: class 1 or 2 (acc. to EN 60228, IEC 60228)
  • Core arrangement: multi-core cable

Application:

Fire resistant E90 cables, that provide security 90 minutes of power supply or controling during a fire. The cables are designed for power supply in buildings with higher requirements of fire protection (skyscrapers, hospitals, shopping centers, tunnels, museums, theaters, cinemas). Cables can be used to supply power and control to receivers (lighting, fire protection appliances, pumps). Cables with electrical support E90 must be installed on appropriate bearing systems tested in accordance with DIN 4102-12. Cables made of halogen-free materials, not emitting harmful substances during a fire. They are suitable for fixed installation in buildings, in industrial equipment, technological lines, machines working in dry and damp rooms - also in public buildings. Cables are suitable for outdoor installation. The outer sheath is UV resistant .