BiT L2 BUS outdoorO2YS(St)C2Y, Data transmission cables for Profibus network, outdoor applicationDownload:Technical data:Basic:
Operating temperature:
Conductor loop resistance (max): 115 Ω/km Screen resistance (max): 9,7 Ω/km Wave attenuation at a frequency: 1 MHz = 1,2 dB/100m 4 MHz = 2,2 dB/100m 10 MHz = 3,2 dB/100m 16 MHz = 4,2 dB/100m Installation details:
Environmental resistance:
Certificates and approvals:
Cable construction:Basic:
Application:The cables are intended for connecting L2-BUS components (standard 485) and transmission of analogue and digital signals. Paired construction ensures good symmetry with respect to earth, while the double screen protects against interferences from external electromagnetic fields, what guarantees very good transmission quality. Cables may be used in dry and damp rooms, outdoor and are suitable for fixed installations. Outer sheath is UV resistant. Cables classified according to EN 50575 (CPR). |