Details

Search results
Visualization Description

IB-BiT 500® 2(St)

Flexible, paired control cables, individually and collectively screened with number coded conductors, for intrinsically safe circuits, rated 300/500V
Industrial application Indoor application Outdoor application UV resistant Vertical flame propagation for a single cable (EN 60332-1) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Oxygen index High flexibility Oil resistance (EN 60811-404) Classified according to EN 50575

Download:

Technical data:

Basic:

  • Cable type: Control / signal cable
  • Operating voltage: 300/500V
  • Test voltage: 50Hz: 3000V
  • Insulation resistance: 20 MΩ x km
  • Inductivity: ~ 0,7mH/km
  • Min. bending radius (flexible connections): 10 x Ø
  • Min. bending radius (fixed installations): 5 x Ø

Operating temperature:

  • Fixed installation: -40℃ do 80℃
  • Flexible connections: -5℃ do 80℃

Installation details:

  • Indoor cable
  • Outdoor cable
  • Min. installation temperature: -5℃

Environmental resistance:

  • Flame retardance on a single wire
  • Flame retardance on a bunched wires
  • UV resistance
  • LOI >29
  • Enhanced oil resistance

Certificates and approvals:

  • CPR Certificates / DoP

Cable construction:

Basic:

  • Conductor: bare copper conductors
  • Conductor stranding: class 5 (acc. to EN 60228, IEC 60228)
  • Screen: double screen
  • Core arrangement: pairs / triples / quads

Application:

Flexible power/control cables designed for operation intrinsically safe circuits. Double screening improves protection of transmitted signals against external electromagnetic field. Individual screening of pairs decreases signal interferences from adjacent pairs. They are suitable for fixed installations and for flexible connections in industrial devices, technological lines and machines operating in dry and damp rooms. Insulation materials and conductor construction in IB-BIT 500® 2(St) cable enable easy and fast connections and ensure their high durability. Cables classified according to EN 50575 (CPR).