BiT 1000®solar H1Z2Z2-K

Flexible single-conductor cables, for photovoltaic systems, acc. to EN 50618, IEC 62930

Indoor application Indoor application
Outdoor application Outdoor application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
High flexibility High flexibility
Oil resistance (EN 60811-404) Oil resistance (EN 60811-404)

Basic

  • Type: Control and power cables
  • Operating voltage: 0,6/1 kV
  • Min. bend radius of permanent connection: 10xØ

Operating temperature

  • Minimum installation temperature: -15°C

Cable construction

  • Conductor material: tinned copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: LSOH
  • Core arrangement: single-core cable
  • Sheath type: LSOH
  • Sheath color: red, black

Fire and functional properties

  • Halogen-free, Low smoke emission EN 61034

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application
  • External application
  • Flexible connections

Environmental resistance

  • O3 – wysoka olejoodporność
  • Oil resistant EN 60811-404
  • UV resistance

Certificates

  • TÜV

BiT 1000®solar H1Z2Z2-K cables are designed to make connections between solar modules and between module sets, as well as to connect module sets to inverter.Thanks to the high environmental strength they are suitable for all kinds of photovoltaic systems, panels mounted on roofs of buildings and extended solar power plants also. The cables are halogen-free and can be safely installed in buildings. Flame propagation on single cable according to EN 60332-1, IEC 60332-1. Cables conform norm EN 50618 and IEC 62930. Estimated operation time: min 25 years. Cables classified according to EN 50575 (CPR).

Cat. no.n x mm2Outer
diameter
[mm]
Approximate cable weight
[kg/km]
Conductor
resistance
at 20 °C
[Ω/km]
Current-carrying
capacity
[A]
blackred
S68201S68201.051×45,4615,0955
S68202S68202.051×66,0803,3970
S68203S68203.051×107,11281,9598
S68204S68204.051×168,21871,24132
S68205S68205.051×2510,43050,795176
S68206S68206.051×3511,73920,565218
S68207S68207.051×5013,75400,393276
S68208S68208.051×7015,67600,277347
S68209S68209.051×9517,69820,21416
S68210S68210.051×12019,012100,164488
S68211S68211.051×15021,715620,132566
S68212S68212.051×18524,818840,108644
S68213S68213.051×24027,024440,0817775
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
BiTinstal® H (p) 450/750V – Safe and Reliable              Installation Cable

BiTinstal® H (p) 450/750V – Safe and Reliable Installation Cable

Safety is a top priority for all of…

Read