BiTflex®(N)TMCGCWOEU

High flexible, medium voltage, screened single core cable based on DIN VDE 0250-813

Industrial application Industrial application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Oxygen index Oxygen index
High flexibility High flexibility
Drag chains Drag chains
Mechanical resistance Mechanical resistance
Oil resistance (EN 60811-404) Oil resistance (EN 60811-404)
Low operating temperature Low operating temperature
Open-pit mining Open-pit mining

Basic

  • Type: Crane cables, Mining cables
  • Operating voltage: 3,6/6 kV, 6/10 kV, 8,7/15 kV, 12/20 kV, 14/25 kV, 18/30 kV

Operating temperature

  • fixed installation from: -50°C
  • fixed installation up to: 80°C
  • flexible connections up to: 80°C

Max. permissible conductor temp.: 90 °C
Max. short-circuit temp. at conductor: 200 °C

Max. tensile load per conductor: 15 N/mm²
Bending radius:
– fixed installation: ≥ 6 x outer-Ø
– free moving: ≥ 8 x outer-Ø

Movement speed (typical values):
– Shore-power systems: 6 m/min
– Energy chains on cranes: 70 – 240 m/min

Cable construction

  • Conductor material: tinned copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: rubber
  • Core arrangement: single-core cable
  • Sheath type: rubber
  • Sheath color: red

Fire and functional properties

  • oxygen index >29

Flame retardant

  • For a single insulated cable

Installation conditions

  • Handling apllications
  • Flexible connections

Environmental resistance

  • Oil resistant EN 60811-404
  • Increased mechanical resistance
  • UV resistance

Additional elements

  • Concentric ground conductor

Certificates

  • UL

Flexible voltage cable used in short lengths, e.g. as a connection in switch-gear or transformer houses where small bending radius is requested. Cable are also used in Onshore-Power-Supply: energy chains, reeling operation or power supply for large electrical applications and drives via cable carrier systems. They are also used in Shore Power System and installed on e.g. port / intermodal cranes.

BiTflex®(N)TMCGCWOEU
3,6/6 kV
Cat. no.n x mm2Maximum
conductor
resistance
Nominal
diameter
over
insulation
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
BM15381×120/160.16420.028-311875383
BM15391×185/250.10824.034-372640510
BM15401×240/250.081726.037-403250607
BiTflex®(N)TMCGCWOEU
6/10 kV
Cat. no.n x mm2Maximum
conductor
resistance
Nominal
diameter
over
insulation
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
BM15501×25/160.79513.021-24790135
BM15511×35/160.56514.522-25920169
BM15521×50/160.39316.024-271130207
BM15531×70/160.27718.026-291375268
BM15541×95/160.21019.028-311635328
BM15551×120/160.16421.029-321905383
BM15561×150/250.13223.032-352315444
BM15571×185/250.10825.034-372670510
BM15581×240/250.081727.037-403290607
BM15591×300/250.065429.040-433935703
BM15601×400/350.049533.043-464915823
BiTflex®(N)TMCGCWOEU
12/20 kV
Cat. no.n x mm2Maximum
conductor
resistance
Nominal
diameter
over
insulation
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
BM15651×25/160.79517.025-281010135
BM15661×35/160.56518.026-291150169
BM15671×50/160.39319.028-311345207
BM15681×70/160.27721.030-331660268
BM15691×95/160.21023.032-351940328
BM15701×120/160.16424.033-362220383
BM15711×150/250.13226.036-392660444
BM15721×185/250.10828.038-413030510
BM15731×240/250.081730.040-433575607
BM15741×300/250.065433.043-464235703
BM15751×400/350.049536.047-505355823
BiTflex®(N)TMCGCWOEU
18/30 kV
Cat. no.n x mm2Maximum
conductor
resistance
Nominal
diameter
over
insulation
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
BM15801×25/160.79520.029-321235135
BM15811×35/160.56521,531-341455169
BM15821×50/160.39323.032-351660207
BM15831×70/160.27725.034-371920268
BM15841×95/160.21026.037-402295328
BM15851×120/160.16428.038-412580383
BM15861×150/250.13230.040-432965444
BM15871×185/250.10832.042-453350510
BM15881×240/250.081734.044-473910607
BM15891×300/250.065436.048-514700703
BM15901×400/350.049540.051-545745823
What Internet Cables to Use? Types of Network Cables. 

What Internet Cables to Use? Types of Network Cables. 

Basic network cables forming the foundation....

Read
Laying Cables in the Ground According to N-SEP-E-004

Laying Cables in the Ground According to N-SEP-E-004

Guidelines for laying electric cables in the ground

Read
Fiber Optic Cables – efficient methods of data transmission

Fiber Optic Cables – efficient methods of data transmission

Fiber optic cables, which gained popularity at the…

Read