NHXCH FE180/PH120/E90 MICA

Fire resistant, halogen-free power cable with concentric conductor

Industrial application Industrial application
Indoor application Indoor application
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Vertical flame spread of vertically-mounted bunched cables (EN 60332-3) Vertical flame spread of vertically-mounted bunched cables (EN 60332-3)
Halogen-free (EN 60754) Halogen-free (EN 60754)
Low smoke emission  (EN 61034) Low smoke emission (EN 61034)
180 min. insulation resistance to fire (IEC 60331) 180 min. insulation resistance to fire (IEC 60331)
90 min. circuit integrity (VDE 4102-12) 90 min. circuit integrity (VDE 4102-12)
Sprinkler zones Sprinkler zones
120 min. circuit integrity (EN 50200) 120 min. circuit integrity (EN 50200)

Basic

  • Type: Fire resistant cables
  • Operating voltage: 0,6/1 kV
  • Voltage test: 4 kV
  • Min. bend radius of permanent connection: 15xØ

Operating temperature

  • fixed installation from: -30°C
  • fixed installation up to: 90°C

Cable construction

  • Conductor material: copper wires
  • Core construction: Class 1 or 2 (according to EN 60228, IEC 60228)
  • Insulation type: LSOH
  • Core arrangement: multi-core cable
  • Sheath type: LSOH
  • Sheath color: orange

Fire and functional properties

  • Fire resistant (IEC 60331), For use in sprinklers zone, Fire integrity function (EN 50200, DIN 4102-12), Halogen-free

Flame retardant

  • For a single insulated cable, For vertically-mounted bunched cables

Installation conditions

  • Internal application

Additional elements

  • Copper wire return

Certificates

  • CNBOP, VDE

Fire resistant power and control cables have E90 fire integrity function which means the assurance of power supply or control under fire conditions for 90 minutes. They are intended for use in buildings with increased fire safety requirements due to high concentration of people, material and cultural assets of high value (sky scrapers, hospitals, shopping centres, tunnels, museums, cinemas, theatres). Cables can be used for power supply or control (lighting, lifts, fire-fighting equipment, pumps). They can be used in fixed installations inside buildings. In case of outdoor application cables should be secured against UV radiation and the external factors. Cables with improved fire characteristic E90 must be installed on the supporting systems tested according to DIN 4102-12.

Cat. no.n x mm2Outer
diameter
[mm]
Approximate
cable weight
[kg/km]
B641503×1,5RE/1,515,3292,3
B641513×2,5RE/2,516,3350,4
B641523x4RE/417,5436,5
B641533x6RE/618,9539,9
B641543x10RE/1021743
B641553x16RM/1624,21097,8
B641563x25RM/1627,91504,9
B641573x35RM/1630,31891,2
B641583x50RM/2535,92599,1
B641593x70RM/3539,43382,3
B641603x95RM/5044,44516,7
B641613x120RM/7049,15598,1
B641623x150RM/7054,46960,9
B641633x185RM/9558,68463,6
B641643x240RM/12066,510840
B641654×1,5RE/1,516,3338
B641664×2,5RE/2,517,4408,7
B641674x4RE/418,7513
B641684x6RE/620,3639,1
B641694x10RE/1022,6886,8
B641704x16RM1626,11320,7
B641714x25RM/1630,51848,6
B641724x35RM/1633,22338,9
B641734x50RM/2539,33216,4
B641744x70RM/3543,24197,7
B641754x95RM/5049,35680,8
B641764x120RM/70546949,5
B641774x150RM/7059,58760,9
B641784x185RM/9564,510634,1
B641794x240RM/12073,313533,1
B641805×2,5RE/2,518,7503,2
B641815x4RE/420,1625,2
B641825x6RE/621,6777,4
B641835x10RE/1024,41077
B641845x16RM/1628,51582,4
B641855x25RM/1633,42267,5
B641865x35RM/1636,42866,1
B641875x50RM/2542,53918,3
B641885x70RM/3547,85202
B641895x95RM/5054,17018,2
B641905x120RM/7058,98698,5
B641915x150RM/7065,610737,8
B641925x185RM/957112993,2
B641937×1,5RE/2,518,8463,9
B641947×2,5RE/2,520561,5
B641957x4RE/421,5714,2
B641967x10RE/1025,91313,5
B641977x16RE/1630,91967
B641987x25RE/1636,72869,6
B641997x35RE/16403611,7
B642007x50RE/2546,74994,4
B642017x70RE/3551,26532
B6420210×1,5RE/2,522,6609,3
B6420310×2,5RE/424,3757,2
B6420410x4RE/626,4967,4
B6420512×1,5RE/2,523,2678,3
B6420612×2,5RE/425851
B6420712x4RE/627,21093,2
B6420814×1,5RE/2,524,3757,4
B6420914×2,5RE/426,1952,9
B6421014x4RE/628,51237,9
B6421119×1,5RE/426,8946,1
B6421219×2,5RE/629,11211,5
B6421319x4RE/10321609,8
B6421424×1,5RE/631,31183,8
B6421524×2,5RE/1034,61576,9
B6421630×1,5RE/633,41392,8
B6421730×2,5RE/1036,41859,4
Fire-resistant Cables and their key role in fire safety

Fire-resistant Cables and their key role in fire safety

Fire-resistant cables are a specialized type of cable…

Read
What Internet Cables to Use? Types of Network Cables. 

What Internet Cables to Use? Types of Network Cables. 

Basic network cables forming the foundation....

Read
How to Select a Servo Cable for a Motor? The most important aspects

How to Select a Servo Cable for a Motor? The most important aspects

Frequency converters play a crucial role in various...

Read