BiTmining®(N)TMCGCWOEU

Medium voltage, screened single core cable based on DIN VDE 0250-813

Industrial application Industrial application
UV resistance UV resistance
Vertical flame propagation for a single cable (EN 60332-1-2) Vertical flame propagation for a single cable (EN 60332-1-2)
Oxygen index Oxygen index
High flexibility High flexibility
Oil resistance (EN 60811-404) Oil resistance (EN 60811-404)
Mining applications Mining applications

Basic

  • Type: Mining cables
  • Min. bending radius of movable connections: ≥ 10xØ
  • Min. bend radius of permanent connection: ≥ 6xØ

Operating temperature

  • fixed installation from: -40°C
  • fixed installation up to: 80°C
  • flexible connections from: -25°C
  • flexible connections up to: 80°C

Max. permissible conductor temp.: 90 °C
Max. short-circuit temp. at conductor: 200 °C
De-rating factors: acc. to DIN VDE 0298-4

Max. tensile load per conductor: 15 N/mm²

Cable construction

  • Conductor material: tinned copper wires
  • Core construction: Class 5 (according to EN 60228, IEC 60228)
  • Insulation type: rubber
  • Sheath type: rubber
  • Sheath color: red

Fire and functional properties

  • oxygen index >29

Flame retardant

  • For a single insulated cable

Installation conditions

  • Internal application
  • External application
  • Flexible connections
  • Mining applications

Environmental resistance

  • Oil resistant EN 60811-404
  • UV resistance

Flexible high voltage cable used in short lengths, e.g. as a connection in switch-gear or transformer houses where small bending radius is requested.

BiTmining®(N)TMCGCWOEU 6/10 kV

n x mm2

Maximum
conductor
resistance
[Ω/km]
Nominal
diameter
over
insulation
[mm]
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
[A]
1×16/161.241220 – 23655116
1×25/160.7951321 – 24785135
1×35/160.5651422 – 25880169
1×50/160.3931624 – 271030207
1×70/160.2771826 – 291305268
1×95/160.2101928 – 311545328
1×120/160.1642129 – 321780383
1×150/250.1322332 – 352240444
1×185/250.1082535 – 382600510
1×240/250.08172737 – 403090607
1×300/250.06542939 – 423865703
1×400/350.04953344 – 474945823
1×500/350.03913546 – 495925946
BiTmining®(N)TMCGCWOEU 8,7/15 kV

n x mm2

Maximum
conductor
resistance
[Ω/km]
Nominal
diameter
over
insulation
[mm]
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
[A]
1×16/161.241220 – 23655116
1×25/160.7951321 – 24785135
1×35/160.5651422 – 25880169
1×50/160.3931624 – 271030207
1×70/160.2771826 – 291305268
1×95/160.2101928 – 311545328
1×120/160.1642129 – 321780383
1×150/250.1322332 – 352240444
1×185/250.1082535 – 382600510
1×240/250.08172737 – 403090607
1×300/250.06542939 – 423865703
1×400/350.04953344 – 474945823
1×500/350.03913546 – 495925946
BiTmining®(N)TMCGCWOEU 12/20 kV

n x mm2

Maximum
conductor
resistance
[Ω/km]
Nominal
diameter
over
insulation
[mm]
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
[A]
1×25/160.7951624 – 27900135
1×35/160.5651726 – 291040169
1×50/160.3931927 – 301220207
1×70/160.2772129 – 321460268
1×95/160.21022.532 – 351785328
1×120/160.1642433 – 362040383
1×150/250.1322635 – 382435444
1×185/250.1082838 – 412895510
1×240/250.08173040 – 433400607
1×300/250.06543242 – 454095703
1×400/350.04953646 – 495180823
1×500/350.03913850 – 536331946
1×630/350.02924455 – 5878781088
BiTmining®(N)TMCGCWOEU 14/25 kV

n x mm2

Maximum
conductor
resistance
[Ω/km]
Nominal
diameter
over
insulation
[mm]
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
[A]
1×25/160.7951826 – 29990135
1×35/160.5651927 – 301110169
1×50/160.3932028 – 311270207
1×70/160.2772231 – 341595268
1×95/160.2102433 – 361865328
1×120/160.1642534 – 372120383
1×150/250.1322737 – 402595444
1×185/250.1082940 – 432985510
1×240/250.08173141 – 443480607
1×300/250.06543344 – 474195703
1×400/350.04953749 – 525420823
1×500/350.03913951 – 546430946
BiTmining®(N)TMCGCWOEU 18/30 kV

n x mm2

Maximum
conductor
resistance
[Ω/km]
Nominal
diameter
over
insulation
[mm]
Outer
diameter
min.-max.
[mm]
Approximate
cable weight
[kg/km]
Current carrying
capacity
[A]
1×25/160.7952028 – 311115135
1×35/160.5652129 – 321220169
1×50/160.3932332 – 351485207
1×70/160.2772433.5 – 36.51750268
1×95/160.2102635 – 382040328
1×120/160.1642737.5 – 40.52380383
1×150/250.1322940 – 432775444
1×185/250.1083242 – 453160510
1×240/250.08173343 – 463675607
1×300/250.06543646 – 494400703
1×400/350.04954051 – 545635823
1×500/350.03914253 – 566660946
Coaxial Cables. Impedance, Attenuation, Applications.

Coaxial Cables. Impedance, Attenuation, Applications.

A coaxial cable is a specialized type of…

Read
Photovoltaic Installations. Cables and panels interconnection.

Photovoltaic Installations. Cables and panels interconnection.

A decade ago, photovoltaic (PV) systems...

Read
Fiber Optic Cables – efficient methods of data transmission

Fiber Optic Cables – efficient methods of data transmission

Fiber optic cables, which gained popularity at the…

Read